Ultrafast Laser Microgrooves for Cold Plates: A Metrology Plan
A microscope image can show that a laser produced a microgroove, but it does not automatically establish the complete channel geometry. Cold plate development needs measurements tied to the intended function and manufacturing stage. Before optimizing a pulse or scan strategy, define what width, depth, sidewall and surface properties must be measured, which regions are accessible and how the sample will be prepared without changing the feature being evaluated.
Liquid Cooling Manufacturing: Laser Processing, Helium Testing & Automation Read the guideOn this page
A microscope image can show that a laser produced a microgroove, but it does not automatically establish the complete channel geometry. Cold plate development needs measurements tied to the intended function and manufacturing stage. Before optimizing a pulse or scan strategy, define what width, depth, sidewall and surface properties must be measured, which regions are accessible and how the sample will be prepared without changing the feature being evaluated.
Translate the feature into measurable definitions
Use the controlled design to identify top width, depth, taper, spacing, position and the relevant surface requirement. Specify where each dimension is taken rather than reporting an unexplained average groove size. Include entrances, exits, turns and other features that matter to the planned fluid path. Separate a dimensional objective from a functional objective: a correctly sized groove still needs the required flow, thermal and joining assessment in the final assembly. This map gives process development a defined target and prevents a favorable image from becoming the entire acceptance criterion.
Choose methods for the geometry they can observe
Match the measurement method to depth, sidewall access, reflectivity and resolution requirements. Optical surface measurement, imaging and prepared sections can provide different evidence; document which method establishes each property. A top view may reveal position or apparent opening but not the full wall or bottom. State any inaccessible or unresolved regions instead of filling them with assumptions. Retain instrument settings, references and sample orientation so that a later comparison measures the same characteristic under a comparable setup.

| Feature property | Definition needed | Method limitation to review |
|---|---|---|
| Opening width | Location and reference edges | Top-view boundary interpretation |
| Depth and wall | Reference plane and section location | Access and steep-sidewall coverage |
| Surface condition | Area, direction and reported quantity | Residue and measurement preparation |
| Repeatability | Sampling across feature and parts | Whether one image represents the population |
Plan sampling before selecting the best region
Choose representative measurement locations before reviewing final images. Include changes in scan direction, repeated passes and relevant start or end regions. Retain sample identity, material, surface preparation and process revision. Use repeats that help separate part-to-part variation from measurement variation. Where a destructive section is used, identify the section location and preparation method, and consider whether preparation can obscure or alter a delicate edge. Keep raw observations with the reported result so a reviewer can understand how the measurement was obtained.
Compare the feature before and after cleaning
Ablation debris or loosely attached material can change the apparent edge or surface. Plan observations before and after the specified cleaning route, with the same definitions and positions where practicable. Record whether a difference reflects removal of residue or a change to the intended substrate; additional evidence may be needed to distinguish them. Include protected joining lands and nearby functional surfaces in the inspection. A cleaning step that reveals a clearer groove can still require evaluation for damage, residue or downstream compatibility.
Connect metrology to the development decision
Summarize which feature requirements were demonstrated, the range examined and the unresolved regions. Decide whether to modify the scan strategy, geometry, cleaning or measurement approach before proceeding to a functional assembly. Keep the result separate from a production-throughput claim. For an AOGEO development review, provide the feature drawing, actual material, sample history and measurement plan. The useful milestone is a documented geometry and cleanliness decision that supports the next trial, not a declaration that one attractive micrograph proves a complete cold plate manufacturing process.
Equipment & systems
Enquiry-only equipment; configuration is defined for the project.
Discuss drawings & process needs ↗Engineering articles & checklists
Explore related guides
Frequently asked questions
Does a top-view micrograph establish groove depth?
Not automatically. Select a method that resolves the required depth and wall geometry and record its limits.
Should only the smoothest region be measured?
No. Use planned representative locations and repeats, including relevant starts, ends and directional changes.
Why measure after cleaning?
Residue can affect apparent geometry and surface results. Check the condition that will enter the next manufacturing operation.
Technical references
TRUMPF: Ultrafast Laser Microprocessing ↗Discuss drawings & process needs
Build project validation around the actual material, joint and inspection conditions.